Exam Cheat Sheet · Quick Reference
Arizona R-11 Electrical Residential
Arizona · PSI Services Contractor
Arizona State Portion 110 questions
Key Distinctions
The main bonding jumper connects the grounded circuit conductor to the equipment grounding conductor at the service, while the system bonding jumper makes the same connection at a separately derived system (e.g., a transformer).
NEC Handbook, Article 100 (Definition: Bonding Jumper, Main)Overload heaters must be sized from the motor's actual nameplate ampere rating to protect the specific motor, whereas branch-circuit conductors and overcurrent protective devices are sized using the full-load current tables (NEC 430.248/430.250).
NEC Handbook, Section 430.32Feeder conductors are sized at 125% of the largest motor's FLC plus the sum of all other motors' FLCs, while the feeder OCPD is sized by taking the largest branch-circuit OCPD rating for any motor and adding the FLC of all other motors.
NEC Handbook, Section 430.24On construction sites, employers may use either GFCIs or an assured equipment grounding conductor program to protect employees from ground faults on branch circuits; they are alternative compliance methods.
29 CFR 1926, §1926.404(b)(1)(i)Under an assured equipment grounding conductor program, fixed cord sets and receptacles not exposed to damage must be tested at intervals not exceeding 6 months, while those exposed to damage must be tested every 3 months.
29 CFR 1926, §1926.404(b)(1)(iii)(E)(4)Type NM cable is permitted for interior use in one- and two-family dwellings including attached/detached garages and storage buildings, whereas Type USE cable is identified for underground use only and shall not be used for interior wiring.
NEC Handbook, Section 334.10(1)For 6 AWG or smaller, the grounded conductor must have a continuous white/gray outer finish or factory-applied stripes (field tape alone is not permitted), while for 4 AWG or larger, identification may be made at the time of installation by a distinctive white or gray marking or tape at its terminations.
NEC Handbook, Section 200.6(A)The EGC is sized based on the rating or setting of the automatic overcurrent device ahead of the equipment (NEC Table 250.122), while the GEC is sized based on the largest ungrounded service conductor (NEC Table 250.66).
NEC Handbook, Section 250.122 / Table 250.122For single-phase circuits, I = (kW × 1000) ÷ (E × PF); for three-phase circuits, I = (kW × 1000) ÷ (E × PF × 1.73), where 1.73 (√3) accounts for the three-phase power relationship.
NEC Handbook, Section 220.5(A)A multiwire branch circuit requires a means that simultaneously disconnects all ungrounded conductors at the point of origin (e.g., a 2-pole breaker or handle-tied single-pole breakers), whereas a standard branch circuit may use an individual single-pole breaker.
NEC Handbook, Section 210.4(B)In a 120/208V three-phase system, phases are black (A), red (B), blue (C), neutral white/gray; in a 277/480V three-phase system, phases are brown (A), orange (B), yellow (C), neutral gray.
NEC Handbook, Section 210.5(C)When 4 to 6 current-carrying conductors are in a raceway, ampacity must be reduced to 80% of the table value; with 3 or fewer current-carrying conductors, no adjustment factor is applied.
NEC Handbook, Table 310.15(C)(1)Key Terms
Formulas to Know
I = (kW × 1000) ÷ (E × PF)I = (kW × 1000) ÷ (E × PF × 1.73)Conductor ampacity = FLC (from NEC table) × 1.25Feeder ampacity = (Largest motor FLC × 1.25) + Sum of all other motors' FLCFeeder OCPD = Largest motor branch-circuit OCPD rating + Sum of all other motors' FLCAdjusted ampacity = Table ampacity × 0.80Energy saved (watts) = Old lamp wattage − New lamp wattageVD = (K × I × L) ÷ CM [K = 12.9 for copper at 75°C; K = 21.2 for aluminum at 75°C]Min conductor ampacity = Noncontinuous load + (Continuous load × 1.25)Min area = Largest ungrounded supply conductor area × 0.125 (12.5%)