Exam Cheat Sheet · Quick Reference
Texas - Master Electrician - Calculations Portion
Texas · PSI Services Contractor
Texas State Portion 33 questions
Key Distinctions
Single-phase uses a multiplier of 2 (VD = 2×K×I×D/CM) because current travels out and back, while three-phase uses 1.732 (VD = 1.732×K×I×D/CM).
Chapter 9 Table 8, Voltage drop formulaSingle-phase uses I = kVA×1000/E (line-to-line voltage only), while three-phase uses I = kVA×1000/(E×√3).
NEC Article 250.30, transformer formula I = kVA × 1000 / EBranch-circuit conductors are sized at 125% of the Table 430.250 FLC value, while overload devices are sized at 125% (SF ≥1.15) of the nameplate current, not the table value.
NEC Table 430.250, Section 430.22, Section 430.6(A)(1)NEC 430.6(A)(1) requires Table 430.250 FLC for sizing branch-circuit conductors and short-circuit protection, while nameplate current is used for sizing overload devices per 430.32.
NEC Table 430.250, Section 430.22, Section 430.6(A)(1)Continuous loads (energized 3+ hours) must be multiplied by 125% when sizing conductors and feeders per NEC 215.2(A)(1) and 230.42(A)(1), while non-continuous loads are calculated at 100%.
NEC 230.42(A)(1)The GEC is sized from Table 250.66 based on the size of the largest service-entrance conductor, while the EGC is sized from Table 250.122 based on the rating of the overcurrent protective device.
NEC Table 250.66Motor feeders (430.24) require 125% of the largest motor FLC plus 100% of all other motor FLCs, while general feeders (215.2) require 125% of continuous loads plus 100% of non-continuous loads.
NEC Table 430.250, Section 430.24For straight pulls the minimum box length = 8 × the largest conduit trade size, while angle pulls use 6 × the largest conduit trade size plus the sum of other conduit sizes on the same wall.
NEC 314.28(A)(1)Per Table 430.52, time-delay fuses are limited to 175% of motor FLC for branch-circuit short-circuit protection, while non-time-delay fuses are permitted up to 300% of motor FLC.
NEC Table 430.250, Table 430.52, Section 240.6(A)When three or more conductors are installed in a raceway, Chapter 9 Table 4 limits fill to 40% of the conduit's cross-sectional area; one conductor uses 53% and two conductors use 31%.
Chapter 9 Table 5, Chapter 9 Table 4The temperature correction factor adjusts conductor ampacity for ambient temperatures above or below 30°C based on insulation rating, while the fill adjustment factor reduces ampacity when more than 3 current-carrying conductors share a raceway.
NEC Table 310.16, Table 310.15(B)(2)(a), Table 310.15(B)(3)(a)THWN conductors are rated 75°C and use the 75°C column of Table 310.16 for ampacity, while THHN conductors are rated 90°C and use the 90°C column, which yields higher base ampacity values.
NEC Table 310.16, Table 310.15(B)(2)(a), Table 310.15(B)(3)(a)Key Terms
Formulas to Know
I = (kVA × 1000) / EI = (kVA × 1000) / (E × √3) [√3 ≈ 1.732]VD = (2 × K × I × D) / CM [K=12.9 copper; D=one-way distance ft; CM from Ch.9 Table 8]VD = (1.732 × K × I × D) / CMMinimum conductor ampacity = FLC(Table 430.250) × 1.25Feeder ampacity = (Largest motor FLC × 1.25) + Σ(all other motor FLCs × 1.00)Adjusted ampacity = Base ampacity(Table 310.16) × Temp correction factor × Fill adjustment factorTotal fill area = Σ(n × area per conductor); Select conduit where 40%-fill capacity ≥ total fill areaI = VA / EI = VA / (E × √3)Min ampacity = (Continuous load × 1.25) + (Non-continuous load × 1.00)Max continuous load = Conductor ampacity / 1.25