Exam Cheat Sheet · Quick Reference
Texas - Journeyman Electrician - Calculations Portion
Texas · PSI Services Contractor
Texas State Portion 26 questions
Key Distinctions
Continuous loads require conductor ampacity of at least 125% of the load current, while non-continuous loads are calculated at 100%.
NEC 215.2(A)(1)(a)Motor-only feeders use 125% of largest motor FLC + 100% of all other motor FLCs, while mixed feeders also add 125% of any continuous non-motor loads.
NEC Table 430.250, Section 430.24A single-motor branch circuit conductor must be ≥125% of that motor's FLC, while a motor feeder must be ≥125% of the largest motor FLC plus 100% of all remaining motor FLCs.
NEC Table 430.248, Section 430.22Temperature correction compensates for ambient heat above the conductor's rated temperature, while conduit fill adjustment derates for heat buildup from multiple current-carrying conductors in the same raceway; both factors are multiplied together against base ampacity.
NEC Table 310.16, Table 310.15(B)(2)(a), Table 310.15(B)(3)(a)Straight pull box minimum length = 8× the largest conduit trade size; angle pull box minimum distance = 6× the largest conduit trade size plus the sum of all other conduit trade sizes on the same wall.
NEC 314.28(A)(1)Single-phase VD uses a factor of 2 in the numerator (VD = 2×K×I×D / CM), while three-phase current uses √3 (1.732) as the divisor (I = VA / (E × 1.732)).
NEC Chapter 9, Table 8Overload protection is set at 125% of the motor nameplate current (for SF ≥1.15), while branch-circuit short-circuit/ground-fault protection via inverse-time CB is set at 250% of the Table FLC (next standard size up if needed).
NEC Section 430.32(A)(1)The disconnect must be rated at least 115% of motor FLC, while branch circuit conductors must have an ampacity of at least 125% of motor FLC.
NEC Table 430.250, Section 430.110(A)Time-delay dual-element fuses are sized at 175% of motor FLC (next standard size up if needed), while inverse-time circuit breakers are sized at 250% of motor FLC (next standard size up if needed).
NEC Table 430.250, Table 430.52, Section 240.6(A)NEC 600.5(A) prohibits other loads on a sign branch circuit (dedicated use only), while NEC 600.5(C) classifies sign loads as continuous, requiring conductor ampacity ≥125% of the sign load.
NEC 600.5(A), 600.5(C)Both use I = VA / (E × √3), but transformer secondary current is calculated from kVA rating to size protective equipment, while system load current is calculated from total calculated VA to size feeder conductors.
NEC Article 700.4, transformer secondary current formulaKey Terms
Formulas to Know
Min Ampacity = (Continuous Load × 1.25) + (Non-Continuous Load × 1.00)Max Continuous Load = OCPD Rating ÷ 1.25Min Ampacity = Motor FLC (from Table) × 1.25Min Ampacity = (Largest Motor FLC × 1.25) + (Sum of All Other Motor FLCs × 1.00)Adjusted Ampacity = Base Ampacity (Table 310.16) × Temperature Correction Factor × Conduit Fill Adjustment FactorVD = (2 × K × I × D) ÷ CM [K = 12.9 copper; I = amps; D = one-way distance (ft); CM = circular mils]I = VA ÷ (E × √3) [√3 ≈ 1.732]I = (kVA × 1000) ÷ (E_secondary × 1.732)Max CB = Motor FLC × 2.50; if result is not a standard size, round UP to next standard size per NEC 240.6(A)Max Fuse = Motor FLC × 1.75; if result is not a standard size, round UP to next standard size per NEC 240.6(A)Total Fill Area = Σ(Number of each conductor × individual conductor area from Table 5); select smallest conduit from Table 4 where 40% fill area ≥ Total Fill Area