Exam Cheat Sheet · Quick Reference
Tennessee - CE - Electrical Contractor
Tennessee · PROV
Tennessee State Portion 100 questions
Key Distinctions
Nontime delay fuses are rated at a maximum of 300% of full-load current, while dual element time-delay fuses are rated at a maximum of 175% of full-load current for single-phase motors.
Ugly's Electrical References, Page 38An inverse time breaker protecting a wound rotor motor is limited to 150% of full-load current, whereas an instantaneous trip breaker for a DC constant voltage motor is limited to 250% of full-load current.
Ugly's Electrical References, Page 38Under 240.4(B), the next higher standard overcurrent device rating above conductor ampacity is permitted up to 800 amperes, but under 240.4(C), when the device exceeds 800 amperes, the conductor ampacity must be equal to or greater than the device rating.
National Electrical Code Handbook, Pages 149-150Emergency power systems transfer within 10 seconds and have more stringent requirements than standby power systems (60-second transfer), and emergency systems are an acceptable alternative where standby systems are required, but not vice versa.
2021 International Building Code, Section 2702.1.7A capacitor-start motor uses a capacitor in series with the starting winding to achieve high starting torque, while a resistance-start motor uses a resistance in series with the starting winding and is used where lower starting torque is acceptable.
NEC Handbook, Section 430.7(A)(9)All 120V, single-phase, 15- and 20-amp receptacle outlets not part of permanent wiring on construction sites require GFCI protection, except receptacles on two-wire, single-phase portable or vehicle-mounted generators rated not more than 5kW where circuit conductors are insulated from the generator frame.
OSHA 1926 CFR 29, Subpart K, §1926.404(b)(1)(ii)Cord sets and receptacles exposed to damage must be tested at intervals not exceeding 3 months, while those that are fixed and not exposed to damage must be tested at intervals not exceeding 6 months under OSHA's assured equipment grounding conductor program.
OSHA 1926 CFR 29, Subpart K, §1926.404(b)(1)(iii)(E)(4)NEC 430.6(A)(1) requires using table values from Tables 430.247–430.250 (not nameplate current) to size branch-circuit conductors and protective devices, while nameplate current is used only for sizing overload protection per 430.6(A)(2).
National Electrical Code Handbook, Page 496, Section 430.6(A)(1)Class II locations are subdivided into material groups (E, F, and G), but Class III locations have no material group designations.
National Electrical Code or National Electrical Code Handbook, Page 622Supplementary overcurrent protection may not be used as a substitute for required branch-circuit overcurrent devices or in place of required branch-circuit protection per NEC 240.10.
National Electrical Code Handbook, Page 151, Section 240.10A white conductor in a cable assembly may be used as a switch leg (ungrounded conductor) only if permanently reidentified at all terminations and visible/accessible locations with a color other than white, gray, or green, and only as the supply to the switch—not as a return conductor.
Nec 2017 Tennessee, Chapter 2, Section 200.7(C)NEC 240.4(D) sets absolute maximum overcurrent ratings for small conductors (e.g., 15A for 14 AWG, 20A for 12 AWG, 10A for 16 AWG copper) regardless of the next-higher-rating permission in 240.4(B).
National Electrical Code Handbook, Page 150Key Terms
Formulas to Know
Feeder ampacity = (125% × largest motor FLC) + sum of all other motor FLCsMax fuse size = FLC × 300%; if result is not a standard size, round UP to next standard size per Table 240.6(A), not to exceed code limitsMax fuse size = FLC × 175%Max breaker size = FLC × 150%Max breaker size = FLC × 250%Max protection per winding = (value from 430.52) × 50% (i.e., ÷ 2)14 AWG Cu → max 15A; 12 AWG Cu → max 20A; 10 AWG Cu → max 30A; 16 AWG Cu → max 10A; 10 AWG Al/Cu-clad Al → max 25AIf OCPD ≤ 800A: next higher standard rating is permitted if conductor ampacity is not already a standard rating; if OCPD > 800A: conductor ampacity ≥ OCPD rating (no rounding up allowed)