Exam Cheat Sheet · Quick Reference
Mississippi Master Electrician
Mississippi · PSI Services Contractor
Mississippi State Portion 80 questions
Key Distinctions
In a series circuit, total resistance equals the sum of all individual resistances (RT = R1+R2+R3), while in a parallel circuit the total resistance is always LESS than the resistance of any single branch.
Ugly's Electrical References, Series CircuitsA continuous load is one where maximum current is expected to continue for 3 hours or more; a non-continuous load does not sustain maximum current for that duration.
NEC Article 100Chapters 1–7 apply broadly to all electrical installations, whereas Chapter 8 (Communications Systems) is NOT subject to Chapters 1–7 requirements except where specifically referenced within Chapter 8.
NEC 90.3General equipment in non-dwelling units requires a warning label for qualified persons; service equipment rated 1200A or more additionally requires a permanent label listing nominal voltage, available fault current, clearing time, and date applied — conductor sizes are NOT required.
NEC 110.16(A)Plug fuses of 15A and lower are identified by a hexagonal window/cap configuration to distinguish them from fuses of higher ampere ratings, which do not use that shape.
NEC 240.50(C)When a switchboard circuit breaker handle operates vertically, the UP position is the closed (ON) position; this directional requirement does not apply to horizontal or rotational handles.
OSHA 1926.404(e)(1)(vi)(B)Kitchen countertop receptacles must be served by at least two 20-ampere small-appliance branch circuits per NEC 210.11(C)(1); a general-purpose 15-ampere circuit is NOT permitted for this use.
NEC 210.11(C)(1), 210.52(B)The first 10 kVA of the general load is calculated at 100%, while any amount above 10 kVA is calculated at only 40%.
NEC 220.82(B)Open conductors not exceeding 150V to ground in pedestrian-only areas need only 3.0 m (10 ft) of clearance, while conductors over public streets and truck-traffic areas require 5.5 m (18 ft).
NEC 225.18(1)Informational notes are included for explanatory purposes only and are NOT enforceable, whereas mandatory rules (shall/shall not language) are legally binding requirements of the Code.
NEC 90.5(C)A multiwire branch circuit must have a means that simultaneously disconnects ALL ungrounded conductors at the point of origin, whereas a single branch circuit requires only one disconnect for its one ungrounded conductor.
NEC 210.4(B)Equipment terminations for circuits over 100 amperes (or conductors larger than 1 AWG) must use conductors rated 75°C (167°F) unless listed for higher; circuits 100A and below may use 60°C-rated conductor ampacity at terminals.
NEC 110.14(C)(1)(b)Key Terms
Formulas to Know
I = E / RE = I × RI = P / ERT = R1 + R2 + R3 + ...KW = (E × I × PF × 1.73) / 1000Total Load = (First 10 kVA × 1.00) + (Remainder × 0.40)Total Load = (First 8 kVA × 1.00) + (Remainder × 0.40)First 3,000 VA at 100%; next 117,000 VA at 35%; remainder at 25%